CONTENTS
FOREWORD 4
1Scope 6
2Normative references 6
3Terms and definitions 7
4Abbreviated terms and symbols 14
4.1General 14
4.2Subscripts 14
4.3Letter symbols 14
4.4Abbreviations 15
5Procedure for insulation co-ordination 15
5.1General outline of the procedure 15
5.2Determination of the representative voltages and overvoltages (Urp) 16
5.3Determination of the co-ordination withstand voltages (Ucw) 18
5.4Determination of the required withstand voltage (Urw) 18
5.5Selection of the rated insulation level 19
5.6List of standard rated short-duration power frequency withstand voltages 20
5.7List of standard rated impulse withstand voltages 20
5.8Ranges for highest voltage for equipment 20
5.9Environmental conditions 20
5.9.1Normal environmental conditions 20
5.9.2Standard reference atmospheric conditions 20
5.10Selection of the standard insulation level 20
5.11Background of the standard insulation level 24
5.11.1General 24
5.11.2Standard rated switching impulse withstand voltage 25
5.11.3Standard rated lightning impulse withstand voltage 25
6Requirements for standard withstand voltage tests 25
6.1General requirements 25
6.2Standard short-duration power-frequency withstand voltage tests 26
6.3Standard impulse withstand voltage tests 26
6.4Alternative test situation 27
6.5Phase-to-phase and longitudinal insulation standard withstand voltage tests
for equipment in range I 27
6.5.1Power-frequency tests 27
6.5.2Phase-to-phase (or longitudinal) insulation lightning impulse tests 28
6.6Phase-to-phase and longitudinal insulation standard withstand voltage tests
for equipment in range II 28
Annex A (normative) Clearances in air to assure a specified impulse withstand voltage
installation 29
A.1General 29
A.2Lightning impulse 30
A.3Switching impulse 31
Annex B (informative) Rated insulation levels for highest voltages of equipment Um
not standardized by IEC 33
Bibliography 34
Figure 1 – Flow chart for the determination of rated or standard insulation level 16
Table 1 – Classes and shapes of overvoltages, Standard voltage shapes and Standard withstand voltage tests 17
Table 2 – Standard insulation levels for range I (1 kV < Um ≤ 245 kV) 22
Table 3 – Standard insulation levels for range II (Um > 245 kV) 23
Table A.1 – Correlation between standard rated lightning impulse withstand voltages
and minimum air clearances 30
Table A.2 – Correlation between standard rated switching impulse withstand voltages
and minimum phase-to-earth air clearances 31
Table A.3 – Correlation between standard rated switching impulse withstand voltages
and minimum phase-to-phase air clearances 32
Table B.1 – Rated insulation levels for highest voltages of equipment Um not standardized by IEC 33
INSULATION CO-ORDINATION –
Part 1: Definitions, principles and rules
1 Scope
This part of IEC 60071 applies to three-phase AC systems having a highest voltage for equipment above 1 kV. It specifies the procedure for the selection of the rated withstand voltages for the phase-to-earth, phase-to-phase and longitudinal insulation of the equipment and the installations of these systems. It also gives the lists of the standard withstand voltages from which the rated withstand voltages are selected.
This document describes that the selected withstand voltages are associated with the highest voltage for equipment. This association is for insulation co-ordination purposes only. The requirements for human safety are not covered by this document.
Although the principles of this document also apply to transmission line insulation, the values of their withstand voltages can be different from the standard rated withstand voltages.
The apparatus committees are responsible for specifying the rated withstand voltages and the test procedures suitable for the relevant equipment taking into consideration the recommendations of this document.
NOTE In IEC 60071-2, all rules for insulation co-ordination given in this document are justified in detail, in particular the association of the standard rated withstand voltages with the highest voltage for equipment. When more than one set of standard rated withstand voltages is associated with the same highest voltage for equipment, guidance is provided for the selection of the most suitable set.
This horizontal standard is primarily intended for use by technical committees in the preparation of standards in accordance with the principles laid down in IEC Guide 108.
One of the responsibilities of a technical committee is, wherever applicable, to make use of horizontal standards in the preparation of its publications. The contents of this horizontal standard will not apply unless specifically referred to or included in the relevant publications.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
IEC 60038, IEC standard voltages
IEC 60060-1, High-voltage test techniques – Part 1: General definitions and test requirements
IEC 60071-2, Insulation co-ordination – Part 2: Application guidelines
IEC 60099-4, Surge arresters – Part 4: Metal-oxide surge arresters without gaps for a.c. systems
Table 2 – Standard insulation levels for range I (1 kV < Um ≤ 245 kV)
Highest voltage for equipment, Um kV (RMS value) | Standard rated short- duration power-frequency withstand voltage kV (RMS value) | Standard rated lightning impulse withstand voltage kV (peak value) |
3,6 |
10 | 20 40 |
7,2 |
20 | 40 60 |
12 |
28 | 60 75 95 |
17,5 a |
38 | 75 95 |
24 |
50 | 95 125 145 |
36 |
70 | 145 170 |
52 a | 95 | 250 |
72,5 | 140 | 325 |
100 b | (150) | (380) |
185 | 450 | |
123 | (185) | (450) |
230 | 550 | |
145 | (185) | (450) |
230 | 550 | |
275 | 650 | |
170 a | (230) | (550) |
275 | 650 | |
325 | 750 | |
245 | (275) | (650) |
(325) | (750) | |
360 | 850 | |
395 | 950 | |
460 | 1 050 | |
NOTE If values in brackets are considered insufficient to prove that the required phase-to-phase withstand voltages are met, additional phase-to-phase withstand voltage tests are needed. | ||
a These Um are non-preferred values in IEC 60038 and therefore seldom used. These values should not be used for new systems to be constructed in future. b This Um value is not mentioned in IEC 60038 but it has been introduced in range I in some apparatus standards. | ||
Table 3 – Standard insulation levels for range II (Um > 245 kV) (1 of 2)
Highest voltage for equipment, Um
kV (RMS value) | Standard rated switching impulse withstand voltage |
Standard rated lightning impulse withstand voltage b
kV (peak value) | ||
Longitudinal insulation a
kV (peak value) |
Phase-to-earth
kV (peak value) |
Phase-to-phase
(ratio to the phase-to-earth peak value) | ||
300 c |
750 |
750 |
1,50 | 850 |
950 | ||||
750 |
850 |
1,50 | 950 | |
1 050 | ||||
362 |
850 |
850 |
1,50 | 950 |
1 050 | ||||
850 |
950 |
1,50 | 1 050 | |
1 175 | ||||
420 |
850 |
850 |
1,60 | 1 050 |
1 175 | ||||
950 |
950 |
1,50 | 1 175 | |
1 300 | ||||
950 |
1 050 |
1,50 | 1 300 | |
1 425 | ||||
550 |
950 |
950 |
1,70 | 1 175 |
1 300 | ||||
950 |
1 050 |
1,60 | 1 300 | |
1 425 | ||||
950 1 050 |
1 175 |
1,50 | 1 425 | |
1 550 | ||||
800 |
1 175 |
1 300 |
1,70 | 1 675 |
1 800 | ||||
1 175 |
1 425 |
1,70 | 1 800 | |
1 950 | ||||
1 175 1 300 |
1 550 |
1,60 | 1 950 | |
2 100 | ||||
1 100 |
– |
1 425 d |
– | 1 950 |
2 100 | ||||
1 425 |
1 550 |
1,70 | 2 100 | |
2 250 | ||||
1 550 |
1 675 |
1,65 | 2 250 | |
2 400 | ||||
1 675 |
1 800 |
1,6 | 2 400 | |
2 550 | ||||
Highest voltage for equipment Um
kV (RMS value) | Standard rated switching impulse withstand voltage |
Standard rated lightning impulse withstand voltage b
kV (peak value) | ||
Longitudinal insulation a
kV (peak value) |
(peak value) Phase-to-earth
kV (peak value) |
Phase-to-phase
(ratio to the phase-to-earth peak value) | ||
1 200 |
1 550 |
1 675 |
1,70 | 2 100 |
2 250 | ||||
1 675 |
1 800 |
1,65 | 2 250 | |
2 400 | ||||
1 800 |
1 950 |
1,60 | 2 550 | |
2 700 | ||||
a Value of the impulse voltage component of the relevant combined test while the peak value of the power-frequency component of opposite polarity is Um ´ 2 3 . b These values apply as for phase-to-earth and phase-to-phase insulation as well; for longitudinal insulation they apply as the standard rated lightning impulse component of the combined standard rated withstand voltage, while the peak value of the power-frequency component of opposite polarity is 0,7 ´ Um ´ 2 3 . c This Um is a non-preferred value in IEC 60038. d This value is only applicable to the phase-to-earth insulation of single phase equipment not exposed to air. | ||||
Bibliography
IEC 60050-614:2016, International electrotechnical vocabulary – Part 614: Generation, transmission and distribution of electricity – Operation
IEC 60507, Artificial pollution tests on high-voltage ceramic and glass insulators to be used on a.c. systems
IEC 60633, High-voltage direct current (HVDC) transmission – Vocabulary
IEC TS 60815-1, Selection and dimensioning of high-voltage insulators intended for use in polluted conditions – Part 1: Definitions, information and general principles
IEC Guide 108, Guidelines for ensuring the coherency of IEC publications – Application of horizontal standards