GOST R 52565, AC circuit-breakers for voltages from 3 to 750 kV. General Specifications

Home Technical

1 Field of application


This Standard is applicable to circuit-breakers (including circuit-breaker drives) designed to switch electrical circuits under normal or emergency conditions in three-phase, 50 Hz AC networks at rated voltage from 3 kV to 750 kV, inclusive.

This Standard is not applicable to special versions of circuit-breaker designed for:

-operation in fire- or explosion-hazardous environment (e.g., in gassy mines);

-frequent switching operations (e.g., in electrothermal plants);

-mobile electric-powered units (e.g., electric locomotives, electric-powered excavators);

-shipboard power installation.

This Standard does not set special requirements for circuit-breakers that work in high seismic conditions. Data about seismic resistance of such circuit-breakers should be given in technical conditions for circuit-breaker of concrete type (TC) and operating documents.


2 Normative reference


This Standard contains references on following normative documents GOST R ISO 90012-2001 Quality management systems. Requirements

GOST 2.601-2006 Unified systems for design documentation. Exploitative documents

GOST 12.2.007.3-75 Occupation safety standards systems. Safety requirements. Electrical devices for voltages above 1000 V

GOST 183-74 Rotating electrical machinery. General specification GOST 982-80 Transformer oils. Specifications

GOST 1516.2-97 Electrical equipment and installations for AC voltages 3 kV and higher.

General methods of dielectric tests

GOST 1516.3-96 Electrical equipment for AC, voltages from 1 to 750 kV. Requirements for dielectric strength of insulation

GOST 10121-76 Transformer oil of selective purification. Specifications

GOST 2991-85 Wooden uncollapsible cases for weights up to 500 kg. General specifications GOST 7746-2001 Current transformers. General specifications

GOST 8024-90 Alternating current apparatus and devices for voltages above 1000 V. Temperature rise at constant duty. Norms and test methods

GOST 9920-89 AC electrical installations for voltage from 3 to 750 kV. Creepage distance of external insulation

GOST 10198-91 Wooden boxes for weights of mass over 200 up to 20000 kg. General specifications

GOST 10434-82 Electric contact connections. Classification. General technical requirements GOST 12969-67 Plates for machines and devices. Technical requirements

GOST 12971-67 Rectangular plates for machines and devices. Dimensions GOST 14192-96 Marking of cargoes

GOST 14254-96 Electrotechnical articles. Enclosures. Degrees of protection. Designations. 

Test methods

GOST 15150-69 Machines, instruments and other industrial articles. Applications for different climatic regions. Categories, operating, storage and transportation conditions as to environment climatic aspects influence

GOST 15543.1-89 Electrical articles. General requirements for environment climatic aspect stability

GOST 16962.1-89 Electrical articles. Test methods as to environment climatic factors resistance

GOST 16962.2-90 Electrical articles. Test methods as to environment mechanical factors stability

GOST 17412-72 Electrical articles for the cold climate regions. Technical requirements, Acceptance and test methods

GOST 17516.1-90 Electrical articles. General technical requirement for environment mechanical stability

GOST 17703-72 Electrical articles for cold climatic regions. Technical requirements, Acceptance and test methods

GOST 18311-80 Electrical products. Terms and definitions of basic concepts

GOST 21130-76 Electrical items. Earth terminals and earth signs. Designs and dimensions GOST 21242-75 Flat or pin contact terminal of electrical equipment. Leading dimensions GOST 24753-81 Contact terminal of electrical equipment. General technical requirements