General Description
  • IEC 60076, ANSI/IEEE Std C57.12, NEMA

  • ISO 9001, KEMA, CESI, CE, TUV, UL, ASTA

  • Mineral Oil / Vegetable Oil (FR3), Free PCB

  • Low loss, Low partial discharge, Low temperature rise

  • Seismic design, ETGI-1.020, IEEE Std 693, NCh2369

  • Structural design, ASTM A325, ANSI/AISC 360, AWS D1.1

  • High altitude correction per IEC 60076 & IEEE C57.12, ~ 5000m

Typical Specification

220kV Three-phase Three-winding Power Transformer with NLTC

Rated Power

(kVA)

Voltage and tapping range(kV)

Vector

group

No-load

loss (kW)

Load loss

(kW)

No-load

current (%)

Impedance (%)

HV

MV

LV

Step Up

Step Down

31500

220±2×2.5%

 

242±2×2.5%

69

 

115

 

121

6.3, 6.6

10.5, 11

35, 37

38.5

YNyn0d11

26.6

137

0.47

HV-MV

22 24

 

HV-LV

12 14

 

MV-LV

7  9

HV-LV

22 24

 

HV-MV

12 14

 

MV-LV

7  9

40000

31.7

161

0.42

50000

37.6

192

0.37

63000

44.5

222

0.37

90000

10.5, 11

13.8, 35

37, 38.5

57

299

0.31

120000

71

369

0.31

150000

11

13.8

15.75

35

37

38.5

84

437

0.26

180000

95

499

0.26

240000

118

614

0.22

300000

139

724

0.18


220kV Three-phase Three-winding Power Transformer with OLTC

Rated Power

(kVA)

Voltage and tapping range(kV)

Vector

group

No-load

loss (kW)

Load loss

(kW)

No-load

current (%)

Impedance (%)

HV

MV

LV

Step Up

Step Down

31500

220±8×1.25%

 

242±8×1.25%

69

 

115

 

121

6.3

6.6

10.5

11

35

37

38.5

YNyn0d11

29.1

138

0.52

HV-MV

22 24

 

HV-LV

12 14

 

MV-LV

7  9

HV-LV

22 24

 

HV-MV

12 14

 

MV-LV

7  9

40000

34.2

161

0.47

50000

40

192

0.42

63000

47

222

0.42

90000

10.5

11

35

37

38.5

62

299

0.37

120000

77

369

0.37

150000

90

437

0.31

180000

103

537

0.31

24000

124

665

0.29