Scope |
|
Main voltage | 3 phase, AC 2.3kV/3kV/3.3kV/4.16kV/6kV/6.6kV/10kV/11kV/13.8kV (-15% to +10%) |
Power range | 100kW – 50000kW |
Overload capacity | 400% full-load current of the motor/60s 500% full-load current of the motor/30s |
Frequency | 50Hz/60Hz ± 2Hz (customised) |
Environmental |
|
Applicable place | Indoor, non-explosive or corrosive gas, low dust |
Ambient operating temperature | 0°C - 40°C (optional - 20°C to 0°C with heaters) |
Humidity | 5% - 95%, non-condensing |
Altitude | < 2000m |
Starting Data |
|
Start current | < 4 rated current of motor (adjustable) |
Start time | 60s (adjustable) |
Start times | 6 times/hour (20°C) |
Control |
|
Control supply voltage | 110V AC/DC or 220V AC/DC, 2000VA (customer supply) |
Power circuit | 18 thyristors, 24 thyristors, 30 thyristors, 36 thyristors, 42 thyristors (model dependent) |
Communication protocol | Modbus RTU, Profibus (option), Ethernet (option) |
Communication interface | RS-485 |
Event history | It can display continuous recording 100 recent events of all kinds of action, such as start, stop, alarm, trip, external fault, etc. |
LCD display | 3.5" |
Cooling | Natural cooling |
Ingress protection of enclosure | IP4X |
Painting | RAL7035 (customised) |
Standards |
|
| The MV Soft Starter is fully EU Compliant IEC EN61800-3: 2004 IEC EN61800-5-1: 2007 |
Protection Parameter |
|
Over-current protection | Over-current alarm and trip setting range: 100 – 300% of full-load current Over-current trip time: 1 - 20 seconds Anti time-limit function |
Under-current protection | Under-current alarm and trip setting range: 10 - 90% of full-load current Over-current trip time: 1 - 60 seconds |
Over-voltage protection | Over-voltage alarm and trip setting range: 100 - 150% of full-load current Over-current trip time: 0.1 - 60 seconds |
Under-voltage protection | Under-voltage alarm and trip setting range: 5 - 90% of full-load current Over-current trip time: 0.1 - 60 seconds |
Motor short-circuit protection | Over-current trip setting range: 300 – 800% of full-load current Short-current trip time: 0 - 3 seconds |
Motor locked-rotor protection | Over-current trip setting range: 300 – 1000% of full-load current Locked- rotor trip time: 1 - 10 seconds |
Phase unbalanced protection | Phase unbalance alarm and trip setting range: 5 - 30% of optional 2 phases unbalance alarm and trip setting time: 1 - 20 seconds |
Load phase-loss protection | Trip value: 10 – 90% FLA Trip time: 1 – 60 seconds |
Power factor protection | Alarm and trip setting range: 0.1 – 1.0 Alarm and trip setting time: 1 – 20 seconds |
Starting overtime protection | Starting time setting range: 1 – 60 seconds |
Start interval protection | Setting range: 1 – 6 times Interval of each task: 0 – 60 minutes |